STUDI ANALISA GANGGUAN HUBUNG SINGKAT 1 FASA KE TANAH PADA SUTT 150 KV UNTUK SETTING RELAY OCR (APLIKASI GI PIP – PAUH LIMO

Amira, Amira ( Institut Teknologi Padang )
Effendi, Asnal ( Institut Teknologi Padang )



Article Info

Publish Date
07 Aug 2014

Abstract

Short circuit was the common disturbance on a power system that increased the current flow causing damage any equipment without a proper protection system. This research was study 1-phase shortcircuit to ground at 10% until 100% transmission length disturbance point and calculate Over Current Relay (OCR) protection setting base on disturbance current occurred. The calculation performed using manual and Matlab software, case study on GI PIP – Pauh Limo, a 22.7 km transmission length. Base on calculation result, it was found that if the disturbance getting closer to the source (disturbance point 10% of transmission length), than disturbance current increased until 147.7758 A. While the disturbance gettingaway from the source (disturbance point 100%), than disturbance current decreased until 147.3853 A. As toprotect the power transmission line from 1-phase short circuit to ground, the 0,65 s OCR setting time should be used at input and output transmission line

Copyrights © 2014






Journal Info

Abbrev

telektro

Publisher

Subject

Computer Science & IT Control & Systems Engineering Electrical & Electronics Engineering Energy Mechanical Engineering

Description

Redaksi Jurnal Teknik Elektro Institut Teknologi Padang mengundang para Peneliti, Akademisi, Praktisi dan Profesional untuk menyumbangkan karya tulisnya, di bidang Teknik Elektro, baik berupa hasil penelitian dan kajian pustaka yang belum pernah dipublikasikan sebelumnya di media lain. ...